Lap splice length for TMT bars per IS 456:2000 Clause 26.2.5.1 — the greater of Ld and the code minimum, with the extra steel the laps add.
A short lap is a structural defect hidden inside concrete: the bar cannot pass its full force to the next bar. A lap that is longer than needed wastes steel on every joint, and a slab or column has hundreds of them. Getting the lap length right for the actual bar, steel and concrete grade avoids both.
A 16 mm Fe500 TMT bar in M25 concrete, flexural tension: σs = 0.87 × 500 = 435 N/mm²; τbd = 1.4 × 1.6 = 2.24 N/mm²; Ld = 16 × 435 / (4 × 2.24) = 777 mm. 30φ = 480 mm, so Ld governs: lap 780 mm (about 49φ). Ten such laps add 0.78 × 1.58 × 10 = 12.3 kg of steel.
Lap bars where stress is low — mid-span for top bars, near supports for bottom bars in continuous beams — and stagger laps so no more than half the bars are lapped at one section. Columns are usually lapped in the middle half of the storey height, as the drawing shows.
Detailers keep a lap table for every bar size and grade combination on the project, print it on the drawings, and check laps during the pre-pour inspection along with cover and spacing.